A 4 IOM-DPCDPR-A: FEB 2014
Appendix Exd0.2
6. How to connect Exd transmitters DPC…, DPR…
Fig. 2.
In case of transmitter calibration outside danger zone is possible communicator connecting to
<SIGNAL+> and <TEST+> terminals. Transmitter is furnished in communication resistor (R
D
= 240Ω),
closed with jumper at <SIGNAL-> and <TEST-> terminals installed by manufacturer. R
D
resistor can be
use then, when it is necessary to communicate with transmitter from its terminals and the load resistance
(Ro) in current loop is lover then 250Ω. Than <SIGNAL-> and <TEST-> terminals have to be open.
Table 1. permitted packing glands
*) for special cable only.
Ex power supply
see p.5..
_
+
TEST
short-circuit( jumper)
Fuse: In = 0,05A, Un = 250V
according to EN 60127
RD
Communicator
Safe area
_
TEST
SIGNAL
_
+
.
32
VWX
MNO
DEF
YZ#
5 6
PQR
*
+/
9
GHI
8 0
@%&
1
4
JKL
7
STU
ABC
RE
F2
PV F4
F3 F4
PF
F1
+
Ro
Hazardous area
E1FW, E1FX/Z,
E2FW, E2FX/Z
PX2K, PXSS2K,
PX2KX, PXB2KX
Kommentare zu diesen Handbüchern