A 14 IOM-DPCDPR-A: FEB 2014
5.4. DPR–2000GALW, Measurement ranges and metrological parameters.
5.4.1 DPR–2000GALW. Measurement ranges
-2,5...2,5mbar (-250...250Pa)
-7...7mbar (-700...700Pa)
-25...25mbar (-2500...2500Pa)
-100...100mbar (-10...10Pa)
5.4.2. DPR–2000GALW. Metrological parameters.
0,1 % (FSO)/ 10C, max 0,4 % (FSO) for the whole thermal compensation
range
Thermal compensation range
Additional electronic damping
5.4.3. DPR–2000GALW. Construction materials
M20x1,5/6x1 adapter brass
Valve manifold ss316L
Valve manifold adapter ss316L
¼ NPT connector brass, ss316L or galvanized St3S carbon steel
(Other materials as given in 5.1.3 for DPR...).
5.4.4. DPR–2000GALW. Pressure Connectors
- The terminals fit adapted to ø 6x1 plastic tubes,
- Valve manifold adapter or ¼ NPT connector- (see p. 8.3. and fig.17).
5.5. DPR–2000YALW. Measurement ranges and metrological parameters.
5.5.1. DPR–2000YALW. Measurement ranges.
5.5.2. DPR–2000YALW. Metrological parameters.
* zeroing in static pressure conditions with zero differential pressure eliminate this error.
Medium density range – up to 1,1 g/cm
3
– (standard version)
– over 1,1 g/cm
3
– (special version by arrangement with DELTA CONTROLS)
Accuracy for minimum range
0,4 % for temperatures –25...+80°C
Zero shift error from static pressure *